| Standard | Resolution 1857 of 2024 — Ministry of Labor |
| Issued | May 27, 2024 · Official Gazette 52,770 of May 28, 2024 |
| In force since | Six months after publication: late November 2024 |
| Applies to | All economic activities that operate or maintain boilers, installed or to be installed |
| Repeals | Articles 500 to 504 of Resolution 2400 of 1979 |
What it regulates and who it applies to
Resolution 1857 of 2024 sets the minimum occupational health and safety requirements for activities involving boilers. It applies to employers, contracting parties, contractors, apprentices and workers in all economic activities that work with any type of boiler, installed or to be installed, and covers the operation and maintenance of the boiler, its auxiliary equipment and the associated pressure piping.
With its issuance, Articles 500 to 504 of Resolution 2400 of 1979 were repealed; for more than four decades they had been the reference for boilers in the Industrial Safety Statute.
The four boiler categories
- Category I: power less than or equal to 50 kW.
- Category II: power greater than 50 kW and up to 1,000 kW.
- Category III: power greater than 1,000 kW and up to 3,000 kW.
- Category IV: power greater than 3,000 kW.
For boilers without a nominal power rating, the resolution provides equivalences by steam generation capacity and by heat transfer area.
The boiler work management program
The employer must implement, maintain and follow up annually on a boiler work management program, integrated into the SG-SST and aligned with the manufacturer’s specifications and technical data sheets. It is built on hazard identification and risk assessment, and covers all workers regardless of their type of employment relationship.
Article 7 sets fifteen minimum contents. Those that require the most work in practice are these:
- Roles and responsibilities, with the training requirements for each role.
- Inventory of routine and non-routine activities, with documented and implemented work procedures.
- Measurement and assessment of exposure, including heat stress, which the resolution requires to be assessed with the WBGT index and other thermal stress indices.
- Prevention and protection measures and emergency procedures.
- Management indicators aligned with Decree 1072 of 2015 and review of results by top management.
Boiler inspection: what must be up to date every year
Items 15 to 18 of Article 12 are the most frequently checked, because they leave dated evidence. All of them require a certificate issued by a natural or legal person accredited by ONAC under ISO/IEC 17025:
| Safety and relief valves | Annual calibration, and also every time they open during operation |
| Boiler | Annual hydrostatic test, before operation |
| Pressure gauges and thermometers | Annual calibration |
| Inlet and outlet piping | Annual hydrostatic test, to ensure tightness |
Two internal controls are added: a checklist for each boiler, its auxiliary equipment and pressure piping, available at the workplace and applied at every shift change; and inspection of prevention and protection equipment by qualified personnel, at the frequency indicated by the manufacturer and at least once a year. Records of inspections and maintenance must be kept.
Other employer obligations that are often left loose
- Qualified personnel: trained or holding a certification of occupational competence, depending on the type of boiler.
- Technical data sheets and manuals in Spanish, required from the manufacturer or supplier, available and understood by workers.
- Communication of procedures to those who carry them out, at every shift change.
- Restricted access: only people authorized by the operations or maintenance manager, the shift supervisor or the SG-SST manager may remain in the boiler area.
- Emergency and rescue plan integrated into the SG-SST plan, with a first aid kit and a support person available for each worker.
- Changes to the boiler approved by a qualified person, ensuring the compatibility of protection components.
- Joint and several liability of the employer for occupational accidents or illnesses resulting from failure to implement these measures.
Who verifies compliance
Inspection, oversight and control are the responsibility of the Ministry of Labor, through the Directorate of Inspection, Oversight and Control, territorial directorates, special offices and municipal inspectorates. Occupational risk insurers (ARLs), for their part, must carry out prevention and advisory activities, exercise delegated oversight and advise employers on the selection of personal protective equipment.
Where to start
- Inventory the boilers, classify them by category and gather their technical data sheets and manuals in Spanish.
- Review the validity of calibration and hydrostatic test certificates, and schedule those missing with bodies accredited by ONAC under ISO/IEC 17025.
- Update the hazard matrix with the hazards listed in the resolution and prioritize them according to actual exposure.
- Document the program with its fifteen minimum contents and integrate it into the SG-SST.
- Put the per-shift checklist, communication of procedures and access control into operation.
- Verify personnel competence and close the cycle with indicators, annual follow-up and management review.
How we support you
Through the PREVI line, we leave the boiler work management program documented and operating within the SG-SST, together with the other high-risk tasks. If you need to know today where your boiler stands against the resolution, the Safe Boiler Operation Inspection (page in Spanish) assesses compliance at three levels and delivers a report with findings, evidence and suggested corrective measures. And if your organization provides calibration or hydrostatic testing services and needs ONAC accreditation under ISO/IEC 17025, the AVALO line supports the accreditation process.
Frequently asked questions
Since when has Resolution 1857 of 2024 been mandatory?
It was published in Official Gazette 52,770 on May 28, 2024 and came into force six months later, in late November 2024. Since then it has been enforceable against every employer that works with boilers.
How often is a boiler hydrostatic test carried out?
Once a year, before operation, with a certificate from a body accredited by ONAC under ISO/IEC 17025. The boiler’s inlet and outlet piping also requires an annual hydrostatic test.
Who can calibrate a boiler’s safety valves?
A natural or legal person accredited by ONAC under ISO/IEC 17025. Calibration is annual and must be repeated every time the valve opens during operation. Pressure gauges and thermometers are also calibrated every year.
Does Resolution 1857 apply to small boilers?
Yes. It applies to any type of boiler, installed or to be installed, in all economic activities. Power determines its category, from I (up to 50 kW) to IV (more than 3,000 kW).
Which regulation did Resolution 1857 of 2024 replace?
It repealed Articles 500 to 504 of Resolution 2400 of 1979, which until then had been the reference for boilers in the Industrial Safety Statute.
Primary sources
Need support on this topic? We offer an initial scope assessment at no cost.
Let’s talk about your case →About the author
ONAC Lead Evaluator since 2012 and ISO Management Systems Lead Auditor since 2005 at accredited certification bodies. Industrial Engineer, Master in Organizational Management and Specialist in Occupational Health and Safety. Graduate professor in specialization and master’s programs at Colombian universities. More than 25 years of experience in manufacturing and services, in the public and private sectors.